Sixnet® EtherTRAK®-2 Revision History

Firmware: 2.03, WebUI: 1.18

2015-06-23

New Features:

ID Subject Description
6759 Firmware Improved Default Gateway Port Support.

Fixed Issues:

ID Subject Description
10062 Web UI Inability to set the scan feature via the Web UI in some situations.
14268 Web UI Limit precision for AI Channel Value to 6 decimal places.
14272 Web UI Fix inability to create tags for AI counters.
14273 Web UI Add TPO channels on AO page when TPO is enabled.
14906 Web UI Fix DI and DO tag names and descriptions not being committed.
14930 Web UI Add option to disable scaling on 10RTD module.
14936 Web UI Remove unprintable character in counters help.
14937 Web UI Fix Test I/O not working in IE 11.

Firmware: 1.26, WebUI: 1.17

2014-11-13

Fixed Issues:

ID Subject Description
12050 Firmware Add cold junction compensation sensor failover and status code.

Firmware: 1.24, WebUI: 1.17

2014-01-03

New Features:

ID Subject Description
6759 Firmware Add support for high speed counters to E2-MIX-20884.
10648 Web UI, Firmware Added analog output range selection of 0 to 5V for E2-MIX-20884.
12050 Firmware Add cold junction compensation sensor failure detection and error code reporting.

Fixed Issues:

ID Subject Description
7711 Web UI Improve web UI to account for the fact that high speed counter channels 3 and 4 share a timebase in the MIX-24882 module. The web UI now propagates the configuration change to both channels when one is changed.
7731 Web UI / OEM Remove unused features from an OEM customized Web UI.
11917 Firmware Return an error when told to create multiple files with the same name because doing so leads to configuration corruption.
11939 Web UI Improve screw terminal assignments and wiring diagram help pages and tables.
11940, 11955 Firmware Add length verification and bounds checking to Modbus messages so that a too-long Modbus message no longer causes a communications failure.
12011 Web UI Clarify wording in analog input integration drop down menus.
12209 Web UI Remove display of module hardware revision.

Firmware: 1.20, WebUI: 1.16

2012-10-09

New Features:

ID Subject Description
10403 Web UI, Firmware Added support for new device: "E2-MIX-20884".
10124 Web UI, Firmware Added new heartbeat configuration settings to the watchdog page.
6812 Web UI Allow dashes in station names.

Fixed Issues:

ID Subject Description
6820 Web UI Fixed selection of analog units in Test I/O - Full Access.
6798 Web UI Fixed issue that caused TPO entries to become enabled when the "Use last 8 discrete channels as outputs" checkbox was checked.

Firmware: 1.15, WebUI: 1.15

2012-08-07

Fixed Issues:

ID Subject Description
8627 Web UI Added the screw terminal assignments for the "E2-16ISOTC".
8626 Web UI Fixed screw terminal list for "E2-16DI24", "E2-16DO24", and "E2-16DIAC".
6391 Web UI For the "E2-16DORLY"; added screw terminal assignments and removed the "Analog input integration" and "Turn OFF outputs on communication loss" options in the "Analog Options" page.

Firmware: 1.15, WebUI: 1.14

2012-01-16

New Features:

ID Subject Description
8628 Web UI Added Analog Input range settings 62.5 mV, 125 mV, and 250 mV for ISOTC modules.
8625 Web UI Added help information for the Thermocouple Analog Input Integration and Temperature Reporting Mode options.

Fixed Issues:

ID Subject Description
7512 Web UI For ET-2 mix modules with 4 high-speed counters, fixed the configuration setting checkbox for the 4th counter.

Firmware: 1.15, WebUI: 1.13

2011-10-18

Fixed Issues:

ID Subject Description
8102 Firmware Fixed spurious ring communications dropouts.

Firmware: 1.14, WebUI: 1.13

2011-10-05

Fixed Issues:

ID Subject Description
8205 Web UI Support 0-20 mA AI configuration in web UI for E2/EB-MIX24882

Firmware: 1.13, WebUI: 1.12

2011-08-31

Fixed Issues:

ID Subject Description
7764 Help Fixed help file's RS-485 lead time and lag time description to match the actual validated values.

Firmware: 1.13, WebUI: 1.11

2011-08-12

Fixed Issues:

ID Subject Description
7146 Web UI Changed watchdog timeout validation to not allow out of range timeout values.
7603 Webserver Added "Cache-Control: no-cache" HTTP header to prevent caching.

Firmware: 1.12, WebUI: 1.10

2011-07-22

New Features:

ID Subject Description
7240 MIX288x modules Added support for high speed counter inputs in latest rev of MIX288x series modules
7139, 7249 E2-16ISO20M Added support for identifying E2-16ISO20M
7126 OEM Added a new OEM

Fixed Issues:

ID Subject Description
7172 TCP/IP Fixed bug where module could reboot if flooded with traffic.

1.11

2011-05-27

New Features:

ID Subject Description
6856 E2-MIX24882 Added 0-20 mA Analog Output Range to E2-MIX24882

1.10

2011-05-10

New Features:

Subject Description
New Modules Added E2/EB-16DORLY, E2/EB-16ISOAI, E2/EB-8ISOAI, E2/EB-16ISOTC, E2/EB-8ISOTC

Fixed Issues:

ID Subject Description
6668 I/O Transfer Fixed failures when using more than 16 I/O transfers
6535, 6554 Modbus UDP Fixed UDP driver creating a Modbus reply header using outdated information.

1.09

2010-08-27

New Features:

Subject Description
Web UI Added compressed web interface support to speed up web UI

Fixed Issues:

ID Subject Description
3198 TCP/IP Fixed issue with out of order TCP/IP packets causing false timeouts.